INFINITY TURBINE · SuperCO2 Data Center System
Infinity Turbine LLC · 30 MW prime power · 800 VDC

SuperCO2 Data Center System: 30 MW Prime Power Plant

A complete natural-gas power plant for an AI data center, built from 64 identical supercritical CO2 turbine modules. It delivers 30 MW straight onto an 800 VDC bus, with no transformers, no medium-voltage switchgear and no AC-to-DC conversion between the generator and the rack.

SuperCO2 30 MW prime power plant with four natural-gas furnace pods, white SuperCO2 module containers, dry coolers and an 800 VDC power house
30.5 MWnet 800 VDC from 60 running modules
40.5%natural gas (LHV) to 800 VDC at ISO conditions
N+464 modules installed; any one can be serviced on line
0 waterclosed CO2 loop, dry-cooled
The plant

Four pods. Sixty-four modules. One DC bus.

Each furnace pod burns pipeline natural gas in four low-NOx burners and heats the CO2 coils of 16 HX-500 power modules. Every module turns that heat into 534 kW of electricity, rectifies it to 800 VDC in its own cabinet, and feeds the pod bus. Four pods give a 30 MW plant that keeps running at about 75% with a whole pod out of service.

  • Native 800 VDC output for next-generation AI racks
  • Higher efficiency than the LM2500 class measured at the DC bus
  • Load following by switching modules, so efficiency stays near 40% at part load
  • Battery storage on each pod bus absorbs AI load steps in milliseconds
  • Built from factory modules in shipping containers, outside the gas turbine delivery queue
Furnace pod cut-away showing radiant coils, convection section, air preheater, SCR, stack and stacked module containers
Efficiency where it counts

Measured at the rack bus

Gas turbines generate medium-voltage AC, which loses about 4% passing through a transformer and a solid-state transformer or rectifier on its way to an 800 VDC rack. The SuperCO2 plant rectifies once, inside each module, at 98.5%.

Fuel to 800 VDC efficiency: JT25 36.0%, LM2500XPRESS+G4 37.8%, SuperCO2 30 MW plant 40.5%

Gas turbine terminal efficiencies (JT25 37.5%, LM2500XPRESS+G4 39.4%) multiplied by 0.985 × 0.975 for conversion to 800 VDC. SuperCO2 figure is from Infinity Turbine's detailed HX-500 design model at ISO 15 °C, to be confirmed by testing.

Plant specification

SuperCO2 30 MW at a glance

ItemMetricImperial / US
Net output30.5 MW at 800 VDC (±400 V)40,800 hp
Fuel to DC efficiency (ISO)40.5% (LHV)heat rate 9,338 Btu/kWh (HHV)
Natural gas7,347 Nm³/h6.58 MMscf/d · 284 MMBtu/h
Power modules64 × HX-500 (60 running + 4 spare)32 × 40 ft containers
Furnace pods4 × 8.1 MW DC, 4 × 5.0 MW burners each17 MMBtu/h per burner
Working fluidCO2, 650 °C, 275 bar1,202 °F, 3,990 psia
NOx / CO2≤ 2.5 ppm with SCR · ≈ 0.50 t/MWh≈ 1,100 lb/MWh
Water consumptionNone (optional adiabatic assist)—
Plot area≈ 87 × 49 m (0.43 ha)≈ 285 × 160 ft (1.1 acre)
Energy storage4 × 2 MWh battery on the pod buses—
Inside the HX-500 module

Three oil-free rotors, two recuperators, one rectifier

HX-500 sCO2 power module on its skid, chrome finish render

Each 5.4 × 2.2 m skid carries a complete recompression Brayton power unit. Two containers' worth of modules sit beside each furnace, so the 650 °C piping stays short.

  • Main compressor spool, 120,000 rpm, on CO2 foil bearings
  • Two-stage recompressor spool, 110,000 rpm
  • Power turbine–generator: two Ø108 mm stages, 534 kW PM generator at 48,000 rpm (800 Hz), magnetic bearings, dry gas seals
  • Printed-circuit recuperators: Alloy 617 high-temperature unit, 316L low-temperature unit
  • 800 VDC SiC active rectifier with solid-state DC breaker
  • Reheat to 650 °C before the power turbine
Heat and power

Burner, coils and 800 VDC electronics

5 MW low-NOx natural gas burner cut-away

5.0 MW low-NOx burner

Staged-fuel burner with swirl register and refractory quarl, firing on 485 °C preheated air. ≤ 9 ppm NOx at the burner, ≤ 2.5 ppm after SCR.

Main heater coil

650 °C heater and reheat coils

Inconel 740H radiant panels and Alloy 625 convection banks heat each module's CO2 to 650 °C. The combustion gas never touches the working fluid.

800 VDC SiC rectifier cabinet

800 VDC rectifier

550 kW silicon-carbide active front end, 98.5% efficient, that also controls generator speed and torque. No transformer, no inverter.

Data sheet

30 MW plant performance by turbine inlet temperature

Turbine inletNet output, 60 modulesFuel → 800 VDCHeat rate Btu/kWh (HHV)Gas MMBtu/h (HHV)Gas MMscf/d
500 °C (932 °F)24.6 MW33.8%11,1832756.37
550 °C (1022 °F)26.7 MW36.3%10,4242786.44
600 °C (1112 °F)28.6 MW38.5%9,8252816.51
650 °C (1202 °F) · optimum30.5 MW40.5%9,3382846.58
700 °C (1292 °F)31.4 MW42.3%8,9332816.49

Fixed hardware, ISO 15 °C ambient, compressor inlet 25 °C. Pipeline gas 1,037 Btu/scf. 650 °C is the optimum: it gives the lowest cost of power and keeps every hot part in code-qualified alloys with margin.

Charts of module output, efficiency and cost of power against turbine inlet temperature
Natural gas

Fuel use and cost, 30 MW at 650 °C

Delivered gas priceFuel cost per hourPer year (8,000 h)Fuel cost per MWh DC
$3.37/MMBtu (EIA 2026 Henry Hub average)$958$7.7 M$31
$4.50/MMBtu (typical delivered industrial)$1,280$10.2 M$42
$6.00/MMBtu (high-cost region)$1,706$13.6 M$56

Against a JT25-class gas turbine at 800 VDC, the plant burns about 11% less gas per MWh delivered to the rack.

Annual fuel cost of a 30 MW plant against delivered gas price, SuperCO2 versus gas turbine
Designed for real sites

Climate and staging

Best in temperate climates

Supercritical CO2 cycles are most efficient in cool air. The plant stays close to its rating up to about 20 °C (68 °F) ambient. On hot sites, adiabatic pre-cooling on the dry coolers or a hot-day rating keeps output predictable.

A three-phase roadmap

Phase 1 is a 600 °C module using existing SuperCO2 500 hardware (about 38.5% to DC). Phase 2 is the 650 °C HX-500 shown here. Phase 3 is a 1 MW module that halves the module count per plant.

HX-500 module front view, chrome finish

Looking for sites, partners and licensees

Infinity Turbine is seeking data center developers, gas suppliers and manufacturing partners for the Phase 1 prototype module and the first pilot pod. A full design package (77 drawing sheets, BOM and data sheet) is available under NDA, and the module and plant designs are available for license.

greg@infinityturbine.com

Performance, emissions and fuel figures are preliminary engineering estimates at ISO conditions (15 °C, sea level) from the Rev A concept design, to be confirmed by detailed design and testing. Gas price cases: EIA November 2026 Short-Term Energy Outlook (Henry Hub $3.37/MMBtu 2026 average) and Infinity Turbine delivered-price assumptions. LM2500 and LM2500XPRESS are products of GE Vernova; JT25 is a product of Jereh Group. Comparisons are for illustration only. See also the SuperCO2 Cluster Mesh concept.