SuperCO2 500 kW Brayton Cycle Turbine
A containerized supercritical CO2 power module that turns heat into electricity, with no steam, no water and no oil. 500 kW per module, built to stack into multi-megawatt plants.
Small turbomachinery. Big output. No water.
Above its critical point (31 °C, 74 bar), CO2 is dense like a liquid but flows like a gas. That density lets a 500 kW machine use turbine wheels smaller than a dinner plate and a compressor impeller about the size of a golf ball. The working fluid stays inside a sealed loop for its whole life. Heat is rejected to air through dry coolers, so the plant needs no cooling tower, no water treatment and no steam boiler operator.
- Closed, sealed CO2 loop: non-flammable, non-toxic, low-cost working fluid
- Oil-free rotating equipment on magnetic and gas foil bearings
- High-speed permanent-magnet generator with grid-tie power electronics
- Factory built and tested, shipped in a standard 20 ft high-cube container
- Modular: add units as heat supply grows, keep running with one unit in service
A simple Brayton cycle, packaged for the field
The SuperCO2 500 runs a closed Brayton cycle, the same thermodynamic cycle used in gas turbines, but with supercritical CO2 as the working fluid and an external heat source instead of a combustor.
Heat in
Your heat source (exhaust gas, flame, molten salt, thermal oil, hot brine) heats the CO2 in a heat exchanger.
Expand
Hot, high-pressure CO2 expands through radial-inflow turbines that drive the 500 kW high-speed generator.
Cool
Dry coolers reject the remaining heat to ambient air. No water is consumed.
Compress
A compact high-speed turbo-compressor returns the dense CO2 to high pressure and the cycle repeats.
Match the module to your heat
Both models share the same 500 kW turbine-generator, oil-free bearing system, power electronics, controls and container, so spares and service are common across a fleet.
High-temperature sources, 400–600 °C
Recuperated Brayton cycle with an Inconel and Alloy 625 hot section. Best efficiency for exhaust gas, flame, molten salt and high-temperature process heat.
- 487 kWe net at 500 °C (932 °F) turbine inlet
- Full 500 kWe from 520 °C (968 °F)
- 30–34% module heat-to-power efficiency
Low-temperature sources, 150–275 °C
Simple Brayton cycle with a two-stage, efficiency-optimised compressor. Built from stainless and 17-4PH steel for lower-grade heat and the tail end of exhaust streams.
- 511 kWe net at 250 °C (482 °F) turbine inlet
- Full 500 kWe from 244 °C (471 °F)
- Lowest cost per kW of the two models
Power from every kind of heat
Figures are per module and assume a heat source about 20–35 °C hotter than the turbine inlet. A site assessment confirms the module count and output for your heat source and climate.
Natural gas
Pair the module with a natural-gas-fired CO2 heater for clean, quiet, water-free prime power, or recover the 450–550 °C exhaust of gas engines and gensets at data centers, compressor stations and industrial sites.
Gas turbine waste heat
Turn simple-cycle gas turbine exhaust into extra power without steam or water. Ideal for mobile and fast-deploy turbines serving AI data centers, oil and gas, and remote grids.
Solar thermal
Run from molten-salt storage at up to 565 °C with the HT model, or from parabolic-trough thermal oil with either model. Thermal storage lets the module deliver dispatchable solar power after sunset.
Biomass
Fire wood chips, agricultural residue or sawmill waste in a hot-gas or thermal-oil heater. No steam boiler means no boiler licence, no water treatment and a smaller operating crew.
Geothermal
Produce power from medium- and high-temperature geothermal brines and steam with a closed, air-cooled loop. No water consumption and nothing released to the air.
Industrial process heat
Recover heat from kilns, furnaces, glass and steel lines, cement and chemical plants. Modules can be added one at a time as heat recovery projects grow.
Output against heat-source temperature
Net electrical output per module at the generator terminals after power electronics and module auxiliaries, with a 25 °C (77 °F) compressor inlet. Dry-cooler fan power is a plant item and is not deducted.
SuperCO2 500 HT
| Turbine inlet | Net output | Efficiency |
|---|---|---|
| 300 °C (572 °F) | 332 kWe | 20.1% |
| 400 °C (752 °F) | 418 kWe | 25.8% |
| 500 °C (932 °F) | 487 kWe | 30.4% |
| 520 °C (968 °F), optimum | 499 kWe | 31.2% |
| 600 °C (1,112 °F) | 542 kWe* | 34.2% |
*Limited by the 550 kW generator peak rating. Optimum is the lowest inlet temperature that reaches the full 500 kWe rating.
SuperCO2 500 LT
| Turbine inlet | Net output | Efficiency |
|---|---|---|
| 100 °C (212 °F) | 125 kWe | 5.6% |
| 150 °C (302 °F) | 303 kWe | 9.3% |
| 200 °C (392 °F) | 423 kWe | 11.1% |
| 244 °C (471 °F), optimum | 501 kWe | 11.8% |
| 250 °C (482 °F), design | 511 kWe | 11.9% |
LT hardware is rated to 275 °C (527 °F); use the HT model above that. The LT model trades efficiency for low cost on heat that would otherwise be wasted.
Technical data
| Item | SuperCO2 500 HT | SuperCO2 500 LT |
|---|---|---|
| Rated output | 500 kWe net (550 kW peak) | 500 kWe net (550 kW peak) |
| Design turbine inlet | 500 °C / 248 bar (932 °F / 3,597 psia) | 250 °C / 198 bar (482 °F / 2,872 psia) |
| Hardware temperature rating | 600 °C (1,112 °F) | 275 °C (527 °F) |
| CO2 flow at design | 5.15 kg/s (11.35 lb/s) | 11.47 kg/s (25.28 lb/s) |
| Compressor inlet | 69.5 bar, 25 °C (1,008 psia, 77 °F) | 69.5 bar, 25 °C (1,008 psia, 77 °F) |
| Cycle | Recuperated Brayton | Simple Brayton |
| Turbine | Two-stage radial inflow, Ø132 mm (5.2 in) wheels, Inconel 718 | Two-stage radial inflow, Ø86.5 mm (3.4 in) wheels, 17-4PH |
| Compressor | Centrifugal, shrouded, 100,000 rpm | Two-stage centrifugal, shrouded, 45,000 rpm |
| Generator | 500 kW permanent-magnet, 36,000 rpm, 600 Hz; active rectifier and grid inverter, 690 V, 50/60 Hz | |
| Bearings and seals | Oil-free: active magnetic bearings and gas foil bearings; dry gas seals | |
| Cooling | Dry coolers (air), no water consumption; glycol loop for generator and electronics | |
| Skid size (L × W × H) | 3.2 × 1.5 × 2.3 m (126 × 59 × 91 in) | 2.8 × 1.5 × 2.3 m (110 × 59 × 91 in) |
| Skid mass | about 3.7 t (8,240 lb) | about 3.2 t (6,970 lb) |
| Enclosure | ISO 20 ft high-cube container, 6.06 × 2.44 × 2.90 m (20 × 8 × 9.5 ft), white with SuperCO2 lettering | |
| Controls | PLC with remote monitoring, automatic start-up and shutdown, grid-forming option, fleet dispatch for multi-module plants | |
Performance is estimated from concept design and will be confirmed by detailed design and factory testing. Specifications are subject to change without notice.
Compact, oil-free turbomachinery






From 500 kW to multi-megawatt: the Cluster Mesh foundation
Each SuperCO2 500 is a complete power plant in a box and the building block of the Infinity Turbine Cluster Mesh system for data center prime power. Group modules on one heat source to build the capacity you need, and keep producing power while any single module is serviced.
- Factory-tested modules cut site work and commissioning time
- N+1 redundancy for high-availability sites such as data centers
- Common spares across HT and LT models
- Relocatable: move modules as heat sources change
Start with a preliminary assessment
Tell us about your heat source: type, temperature, flow and site climate. Our paid Preliminary Assessment sizes the SuperCO2 500 modules for your site, estimates output and budget cost, and sets out the path to a project.